About Us

About Master Exhaust House

We move air out of the places where work gets done.

Industrial ventilation and evaporative cooling equipment for Bangladesh — exhaust fans, air coolers, dehumidifiers and air curtains, sized to the building rather than picked off a catalogue page.

Dhaka, Bangladesh Unit 2 Ventilation & industrial cooling +880 1706-259292

Who we are

A ventilation supplier that asks about your floor before it quotes.

Master Exhaust House supplies, installs and services industrial ventilation and cooling equipment for factories, warehouses, poultry sheds and commercial buildings across Bangladesh. Our range covers heavy-duty exhaust fans, cone fans, evaporative air coolers, industrial dehumidifiers and air curtains.

Most ventilation problems we are called in to fix are not equipment failures. They are sizing failures — a fan rated for a storeroom installed on a 900 m² production floor, or a cooler placed where the air has nowhere to leave. So we start with the room: its area, its height, what happens inside it, and how many times an hour that air needs replacing. The equipment follows from the number.

That is also why every quotation we send names the airflow figure it is built on. If the assumption is wrong, you can see it before the units are on site rather than after.

Established
year
Head office
street address, Dhaka
Coverage
Nationwide, Bangladesh
Team
no. of staff — sales, technical, installation
Categories
Exhaust fans · Air coolers · Dehumidifiers · Air curtains
Phone
+880 1706-259292
Email
masterexhausthouse@gmail.com

What we supply

The range, by what it can actually move.

Equipment is grouped by capacity, not by model name — because the first question in any enquiry is how much air has to shift, and how large a space it has to serve.

EquipmentCapacityTypically installed in
Industrial exhaust fanairflow range m³/hrProduction floors, warehouses, workshops
Cone exhaust fanairflow range m³/hrPoultry sheds, greenhouses, large open spans
Evaporative air cooler18,000 – 30,000 m³/hrOpen and semi-open workspaces, assembly halls
Industrial dehumidifier60 – 480 L/dayStorage rooms, humidity-sensitive production
Air curtainwidth / speedEntrances, loading bays, cold-room doors
Ventilation fanairflow range m³/hrKitchens, welding bays, enclosed utility rooms

How a system gets sized

Three numbers decide the fan. Everything else is selection.

Required airflow (m³/hr)
= floor area (m²)
× ceiling height (m)
× air changes per hour (ACH)

Air changes per hour is the only judgement call in the formula, and it comes from what the space is used for — not its size. A cold store and a welding bay of identical volume need very different fans.

Warehouse 15–20 ACH Garments floor 30–40 Poultry shed 35–45 Commercial kitchen 40–60 Welding bay 50–60

Worked example — garments floor

Floor area
900 m²
Ceiling height
3.5 m
Volume
3,150 m³
Air changes per hour
30
Required airflow
94,500 m³/hr

Covered by three exhaust fans at roughly 32,000 m³/hr each, positioned against the prevailing inlet side so the air crosses the floor instead of short-circuiting back out.

How an order runs

From enquiry to handover, in four stages.

01

Site details

Floor area, height, what is produced inside, existing openings, and power available. A phone call is usually enough; for larger floors we visit.

02

Sizing and quotation

We calculate the airflow requirement and quote the unit count and model against it. The airflow figure is printed on the quotation so the assumption is visible.

03

Supply and installation

Delivery and fitting by our own installation team, including opening preparation, mounting frames and electrical connection.

04

Service and spares

Replacement pads, belts, motors and pumps held for the models we supply, with servicing on call after handover.

Where our equipment runs

Industries we supply across Bangladesh.

Garments & textile Poultry & livestock Food processing Warehousing & logistics Pharmaceuticals Plastic & packaging Workshops & garages Commercial kitchens Showrooms & retail Cold storage

Get in touch

Tell us the room. We will size the system.

Floor area, ceiling height and what happens inside — that is enough to come back with an airflow figure and a unit count.

Request a quotation →
Phone +880 1706-259292 Email masterexhausthouse@gmail.com Office Dhaka, Bangladesh Hours Sat – Thu, 9:00 – 18:00
Scroll to Top